PRODUCT NAME | 50KVA Industrial Digital UPS | |
Model | ET50K | |
Power Capacity | 50KVA/50KW | |
Power Factor | 1.0 | |
Dimension(DxWxH mm) | 700x600x1600mm | |
Weight(Kgs) | 320KGS | |
INPUT | ||
Input Phase Number | 3 Phases 5 Wires(3PH+N+PE) | |
Input Rated Voltage | 380VAC/400VAC/415VAC (Default 380VAC) | |
Variable Input Voltage Range | 304V-456V | |
Input Frequency Variation Range | 40Hz- 70Hz | |
Input Power Factor | ≥0.95 | |
Input Current Limit | 1.25 times of the rated current ( 0.1- 1.25 can be set) | |
Rectifier Delay Start Range | Default 10S (1 -300 S can be set) | |
Battery Voltage | Default 360VDC ( 336VDC, 384VDC, 372VDC, 384VDC can be set) | |
Battery Charging Current | Charge rate X battery capacity X battery pack number | |
OUTPUT | ||
Output Phase Number | 3 Phases 5 Wires(3PH+N+PE) | |
Rated Output Voltage | 380VAC/400VAC/415VAC (Default 380VAC) | |
Output Voltage Regulation Accuracy | ± 1% | |
Output Frequency Accuracy | Mains mode: tracking bypass input in synchronization state; battery mode: 50Hz/60Hz±0.1% | |
Output Waveform Distortion | Resistive load ≤2% ; Non-linear load≤5% | |
Waveform | Pure Sine Wave | |
Output Current Crest Factor | 3:1 | |
Output Power Factor | 1.0 | |
Overload Capacity | When the load is <105%, it can work for a long time; when 125%<load<150%, switch to bypass output after 1 minute; when load>150%, switch to bypass output after 200 miliseconds. | |
SYSTEM INDICATORS | ||
System Efficiency | Online mode: >93%, ECO mode: >98% | |
Switching Time | 0ms | |
Number of Parallel | ≤ 8 sets | |
Protective Function | Output short circuit protection, output overload protection, over temperature, battery low voltage protection, output overvoltage and under voltage protection, fan failure protection, etc. | |
Communication Interface | Standard configuration: USB, CAN, EPO, RS232, RS485, dry contact; Optional configuration: SNMP card, temperature compensation accessories. | |
Display | 7 inch LCD touch screen | |
WORKING ENVIRONMENT | ||
Operating Temperature | 0℃ to 40℃ | |
Storage Temperature | -25℃ to 55℃ ( exclude battery) | |
Relative Humidity | 0%~95% (No condensation) | |
Altitude | Altitude ≤1000M, exceed 1000M, Power with increase of 100M will reduce 1% | |
Degree of protection | IP30 | |
Noise | < 65dB (1 meter from device) |